An Optical Voltage Sensor Based on Piezoelectric Thin Film for Grid Applications
Authors:
Jordan L. Edmunds,
Soner Sonmezoglu,
Julien Martens,
Alexandra Von Meier,
Michel M. Maharbiz
Abstract:
Continuous monitoring of voltages ranging from tens to hundreds of kV over environmental conditions, such as temperature, is of great interest in power grid applications. This is typically done via instrument transformers. These transformers, although accurate and robust to environmental conditions, are bulky and expensive, limiting their use in microgrids and distributed sensing applications. Her…
▽ More
Continuous monitoring of voltages ranging from tens to hundreds of kV over environmental conditions, such as temperature, is of great interest in power grid applications. This is typically done via instrument transformers. These transformers, although accurate and robust to environmental conditions, are bulky and expensive, limiting their use in microgrids and distributed sensing applications. Here, we present a millimeter-sized optical voltage sensor based on piezoelectric aluminum nitride (AlN) thin film for continuous measurements of AC voltages <350kVrms (via capacitive division) that avoids the drawbacks of existing voltage-sensing transformers. This sensor operated with 110uW incident optical power from a low-cost LED achieved a resolution of 170mVrms in a 5kHz bandwidth, a measurement inaccuracy of 0.04% due to sensor nonlinearity, and a gain deviation of +/-0.2% over the temperature range of ~20-60C. The sensor has a breakdown voltage of 100V, and its lifetime can meet or exceed that of instrument transformers when operated at voltages <42Vrms. We believe that our sensor has the potential to reduce the cost of grid monitoring, providing a path towards more distributed sensing and control of the grid.
△ Less
Submitted 23 July, 2021;
originally announced August 2021.
-
Topology Detection in Microgrids with Micro-Synchrophasors
Authors:
Reza Arghandeh,
Martin Gahr,
Alexandra von Meier,
Guido Cavraro,
Monika Ruh,
Göran Andersson
Abstract:
Network topology in distribution networks is often unknown, because most switches are not equipped with measurement devices and communication links. However, knowledge about the actual topology is critical for safe and reliable grid operation. This paper proposes a voting-based topology detection method based on micro-synchrophasor measurements. The minimal difference between measured and calculat…
▽ More
Network topology in distribution networks is often unknown, because most switches are not equipped with measurement devices and communication links. However, knowledge about the actual topology is critical for safe and reliable grid operation. This paper proposes a voting-based topology detection method based on micro-synchrophasor measurements. The minimal difference between measured and calculated voltage angle or voltage magnitude, respectively, indicates the actual topology. Micro-synchrophasors or micro-Phasor Measurement Units (μPMU) are high-precision devices that can measure voltage angle differences on the order of ten millidegrees. This accuracy is important for distribution networks due to the smaller angle differences as compared to transmission networks. For this paper, a microgrid test bed is implemented in MATLAB with simulated measurements from μPMUs as well as SCADA measurement devices. The results show that topologies can be detected with high accuracy. Additionally, topology detection by voltage angle shows better results than detection by voltage magnitude.
△ Less
Submitted 7 January, 2015;
originally announced February 2015.
-
Phase Identification in Distribution Networks with Micro-Synchrophasors
Authors:
Miles H. F. Wen,
Reza Arghandeh,
Alexandra von Meier,
Kameshwar Poolla,
Victor O. K. Li
Abstract:
This paper proposes a novel phase identification method for distribution networks where phases can be severely unbalanced and insufficiently labeled. The analysis approach draws on data from high-precision phasor measurement units (micro-synchrophasors or uPMUs) for distribution systems. A key fact is that time-series voltage phasors taken from a distribution network show specific patterns regardi…
▽ More
This paper proposes a novel phase identification method for distribution networks where phases can be severely unbalanced and insufficiently labeled. The analysis approach draws on data from high-precision phasor measurement units (micro-synchrophasors or uPMUs) for distribution systems. A key fact is that time-series voltage phasors taken from a distribution network show specific patterns regarding connected phases at measurement points. The algorithm is based on analyzing crosscorrelations over voltage magnitudes along with phase angle differences on two candidate phases to be matched. If two measurement points are on the same phase, large positive voltage magnitude correlations and small voltage angle differences should be observed. The algorithm is initially validated using the IEEE 13-bus model, and subsequently with actual uPMU measurements on a 12-kV feeder.
△ Less
Submitted 7 January, 2015;
originally announced January 2015.
-
Chapter 34 - Every Moment Counts: Synchrophasors for Distribution Networks with Variable Resources
Authors:
Alexandra von Meier,
Reza Arghandeh
Abstract:
Historically, with mostly radial power distribution and one-way power flow, it was only necessary to evaluate the envelope of design conditions, e.g., peak loads or fault currents, rather than continually observe the operating state. But the growth of distributed energy resources introduces variability, uncertainty, and opportunities to recruit diverse resources for grid services. This chapter add…
▽ More
Historically, with mostly radial power distribution and one-way power flow, it was only necessary to evaluate the envelope of design conditions, e.g., peak loads or fault currents, rather than continually observe the operating state. But the growth of distributed energy resources introduces variability, uncertainty, and opportunities to recruit diverse resources for grid services. This chapter addresses how the direct measurement of voltage phase angle might enable new strategies for managing distribution networks with diverse, active components.
△ Less
Submitted 7 August, 2014;
originally announced August 2014.