An Integrated Transportation Network and Power Grid Simulation Approach for Assessing Environmental Impact of Electric Vehicles
Authors:
Diana Wallison,
Jessica Wert,
Farnaz Safdarian,
Komal Shetye,
Thomas J. Overbye,
Jonathan M. Snodgrass,
Yanzhi Xu
Abstract:
This study develops an integrated approach that includes EV charging and power generation to assess the complex cross-sector interactions of vehicle electrification and its environmental impact. The charging load from on-road EV operation is developed based on a regional-level transportation simulation and charging behavior simulation, considering different EV penetration levels, congestion levels…
▽ More
This study develops an integrated approach that includes EV charging and power generation to assess the complex cross-sector interactions of vehicle electrification and its environmental impact. The charging load from on-road EV operation is developed based on a regional-level transportation simulation and charging behavior simulation, considering different EV penetration levels, congestion levels, and charging strategies. The emissions from EGUs are estimated from a dispatch study in a power grid simulation using the charging load as a major input. A case study of Austin, Texas is performed to quantify the environmental impact of EV adoption on both on-road and EGU emission sources at the regional level. The results demonstrate the range of emission impact under a combination of factors.
△ Less
Submitted 2 April, 2025;
originally announced April 2025.
-
Electric Vehicle Integration using Large-Scale Combined Transmission and Distribution Grid Models
Authors:
Diana Wallison,
Lyric Haylow,
Jessica Wert,
Jonathan M. Snodgrass,
Thomas J. Overbye,
Yanzhi,
Xu
Abstract:
In this paper, we propose a unifying co-simulation framework integrating transportation demand, grid assets, land use, demographics, and emissions to optimally accelerate electric vehicle (EV) development as well as measure the impact of EV integration. 96 urban and long-haul truck charging demand simulations were developed and integrated into a combined transmission and distribution (T&D) simulat…
▽ More
In this paper, we propose a unifying co-simulation framework integrating transportation demand, grid assets, land use, demographics, and emissions to optimally accelerate electric vehicle (EV) development as well as measure the impact of EV integration. 96 urban and long-haul truck charging demand simulations were developed and integrated into a combined transmission and distribution (T&D) simulation, encompassing the Houston/Dallas/Fort Worth area. The T&D scenarios are then used to develop cost optimization strategies to determine optimal placement and sizing of truck charging infrastructure that minimize infrastructure costs.
△ Less
Submitted 21 March, 2025;
originally announced March 2025.
-
The Effects of Correctly Modeling Generator Step-Up Transformer Status in Geomagnetic Disturbance Studies
Authors:
Jessica L. Wert,
Pooria Dehghanian,
Jonathan Snodgrass,
Thomas J. Overbye
Abstract:
In order to correctly model the impacts of geomagnetically induced current (GIC) flows, the generator step-up (GSU) transformer status must be properly modeled. In power flow studies, generators are typically removed from service without disconnecting their GSU transformers since the GSU transformer status has little to no impact on the power flow result. In reality, removing a generator from serv…
▽ More
In order to correctly model the impacts of geomagnetically induced current (GIC) flows, the generator step-up (GSU) transformer status must be properly modeled. In power flow studies, generators are typically removed from service without disconnecting their GSU transformers since the GSU transformer status has little to no impact on the power flow result. In reality, removing a generator from service involves also removing its GSU transformer from service. This difference presents a discrepancy between simulated behavior and system observations during geomagnetic disturbance (GMD) events. This paper presents GMD case studies on 2000-bus and 24,000-bus systems in which reactive power losses and geomagnetically induced currents are compared across scenarios in which the GSU transformers for the disconnected generators are either in-service or out-of-service. The results demonstrate a 3.2 to 15.5 percent error in reactive power losses when the GSU status is modeled incorrectly. Discrepancies of up to 95 A per phase for branch GIC flows and 450 A for transformer neutral GIC flows are also observed and visualized.
△ Less
Submitted 23 August, 2022;
originally announced August 2022.
-
Application of Transformer Impedance Correction Tables in Power Flow Studies
Authors:
Pooria Dehghanian,
Ju Hee Yeo,
Jessica Wert,
Hanyue Li,
Komal Shetye,
Thomas J. Overbye
Abstract:
Phase Shifting Transformers (PST) are used to control or block certain flows of real power through phase angle regulation across the device. Its functionality is crucial to special situations such as eliminating loop flow through an area and balancing real power flow between parallel paths. Impedance correction tables are used to model that the impedance of phase shifting transformers often vary a…
▽ More
Phase Shifting Transformers (PST) are used to control or block certain flows of real power through phase angle regulation across the device. Its functionality is crucial to special situations such as eliminating loop flow through an area and balancing real power flow between parallel paths. Impedance correction tables are used to model that the impedance of phase shifting transformers often vary as a function of their phase angle shift. The focus of this paper is to consider the modeling errors if the impact of this changing impedance is ignored. The simulations are tested through different scenarios using a 37-bus test case and a 10,000-bus synthetic power grid. The results verify the important role of impedance correction factor to get more accurate and optimal power solutions.
△ Less
Submitted 2 September, 2020;
originally announced September 2020.