Joint Estimation of System Inertia and Load Relief
Authors:
Julius Susanto,
Alireza Fereidouni,
Dean Sharafi
Abstract:
Modern power systems with high share of renewable generation are at the risk of rapid changes in frequency and inertia resulting from contingencies. The importance of an accurate assessment of system and load relief, as well as frequency changes in the critical timescales is more pronounced in these power systems. This knowledge serves as an insight which will guide the solutions required for enha…
▽ More
Modern power systems with high share of renewable generation are at the risk of rapid changes in frequency and inertia resulting from contingencies. The importance of an accurate assessment of system and load relief, as well as frequency changes in the critical timescales is more pronounced in these power systems. This knowledge serves as an insight which will guide the solutions required for enhanced security and resilience. A novel procedure for simultaneously assessing system inertia and load relief using a closed-form system frequency response (SFR) model to fit measured disturbance data is presented. Results of applying the proposed approach on generator contingencies in the South West Interconnected System (SWIS) in Western Australia demonstrate the validity of the method and indicate that it can overcome some of the limitations observed in conventional inertia estimation methods based on the linearised swing equation, such as the sliding window and polynomial fit methods.
△ Less
Submitted 1 October, 2021;
originally announced October 2021.
-
Online Security Assessment of Low-Inertia Power Systems: A Real-Time Frequency Stability Tool for the Australian South-West Interconnected System
Authors:
Alireza Fereidouni,
Julius Susanto,
Pierluigi Mancarella,
Nicky Hong,
Teresa Smit,
Dean Sharafi
Abstract:
In small/medium-sized isolated power networks with low rotational inertia and high penetration of renewables, generation/load contingency events may cause large frequency excursions, potentially leading to cascading failures and even blackouts. Therefore, it is crucial for system operators to be able to monitor the state of the network in real-time and predict the maximum possible frequency deviat…
▽ More
In small/medium-sized isolated power networks with low rotational inertia and high penetration of renewables, generation/load contingency events may cause large frequency excursions, potentially leading to cascading failures and even blackouts. Therefore, it is crucial for system operators to be able to monitor the state of the network in real-time and predict the maximum possible frequency deviations at all times.
This paper presents a real-time frequency stability (RTFS) tool developed by the Australian Energy Market Operator (AEMO) and operationalized in the control room for the South West Interconnected System (SWIS) to ensure that the available spinning reserve is sufficient and fast enough to arrest frequency excursions under any conditions, and particularly low-inertia ones. To reduce the computational burden and complexity of the different turbine-governor models, a simple first-order lag function with two adjustable variables has been used for each of the generator. These adjustable parameters, along with other key model parameters such as load damping and inertia, have been calibrated against actual frequency response using high-speed fault recorder data from historical events. As demonstrated in several case studies, the real-time tool has proven to be accurate at predicting the trajectory of system frequency after credible contingencies, thus suggesting that similar implementations could be carried out elsewhere while power systems worldwide progress towards lower inertia.
△ Less
Submitted 26 October, 2020;
originally announced October 2020.
-
Closed-Form Solutions for a Low-Order System Fast Frequency Response Model
Authors:
Julius Susanto,
Alireza Fereidouni,
Pierluigi Mancarella,
Dean Sharafi
Abstract:
This paper presents a novel closed-form solution for a low-order system frequency response (SFR) model that is accurate for all time periods and an accompanying approximation for representing primary frequency responses at two different speeds while still maintaining mathematical tractability. This allows for the inclusion of both fast frequency responses (e.g. from battery energy storage systems)…
▽ More
This paper presents a novel closed-form solution for a low-order system frequency response (SFR) model that is accurate for all time periods and an accompanying approximation for representing primary frequency responses at two different speeds while still maintaining mathematical tractability. This allows for the inclusion of both fast frequency responses (e.g. from battery energy storage systems) and more conventional responses (e.g. from thermal generation) in a single SFR formulation. The closed-form expressions can be efficiently used in applications that use the SFR model such as frequency stability studies and security-constrained unit commitment (SCUC) studies.
△ Less
Submitted 26 October, 2020;
originally announced October 2020.
-
Optimal Capacity of a Battery Energy Storage System based on Solar Variability Index to Smooth out Power Fluctuations in PV-Diesel Microgrids
Authors:
Julius Susanto,
Farhad Shahnia
Abstract:
Battery energy storage systems can be integrated with photovoltaic (PV)-diesel microgrids, as an enabling technology to increase the penetration of PV systems and aid microgrid stability by smoothing out the power fluctuations of the PV systems. The aim of this paper is to derive correlations between the optimal capacity of the smoothing batteries and variabilities in daily solar irradiance. Two c…
▽ More
Battery energy storage systems can be integrated with photovoltaic (PV)-diesel microgrids, as an enabling technology to increase the penetration of PV systems and aid microgrid stability by smoothing out the power fluctuations of the PV systems. The aim of this paper is to derive correlations between the optimal capacity of the smoothing batteries and variabilities in daily solar irradiance. Two commonly used smoothing techniques of moving average and ramp rate control are applied on a real solar irradiance dataset with a 1-minute resolution for a full calendar year across 11 sites in Australia. The paper then presents the developed empirical model, based on linear regressions, to estimate the optimal capacity of the batteries without requiring the use of detailed simulation studies. The performance of the developed technique is validated by numerical simulation studies in MATLAB. The study demonstrates that the empirical model provided reasonably accurate estimates when using the moving average smoothing technique, but had limited accuracy under the ramp rate control technique.
△ Less
Submitted 25 June, 2020;
originally announced June 2020.
-
Improved Parameter Estimation Techniques for Induction Motors using Hybrid Algorithms
Authors:
Julius Susanto,
Syed Islam
Abstract:
The performance of Newton-Raphson, Levenberg-Marquardt, Damped Newton-Raphson and genetic algorithms are investigated for the estimation of induction motor equivalent circuit parameters from commonly available manufacturer data. A new hybrid algorithm is then proposed that combines the advantages of both descent and natural optimisation algorithms. Through computer simulation, the hybrid algorithm…
▽ More
The performance of Newton-Raphson, Levenberg-Marquardt, Damped Newton-Raphson and genetic algorithms are investigated for the estimation of induction motor equivalent circuit parameters from commonly available manufacturer data. A new hybrid algorithm is then proposed that combines the advantages of both descent and natural optimisation algorithms. Through computer simulation, the hybrid algorithm is shown to significantly outperform the conventional algorithms in terms of convergence and squared error rates. All of the algorithms are tested on a large data set of 6,380 IEC (50Hz) and NEMA (60Hz) motors.
△ Less
Submitted 7 April, 2017;
originally announced April 2017.