Identification of Power System Dynamic Model Parameters using the Fisher Information Matrix
Authors:
Dawn Virginillo,
Asja Derviškadić,
Mario Paolone
Abstract:
The expected decrease in system inertia and frequency stability motivates the development and maintenance of dynamic system models by Transmission System Operators. However, some dynamic model parameters can be unavailable due to market unbundling, or inaccurate due to aging infrastructure, non-documented tuning of controllers, or other factors. In this paper, we propose the use of a numerical app…
▽ More
The expected decrease in system inertia and frequency stability motivates the development and maintenance of dynamic system models by Transmission System Operators. However, some dynamic model parameters can be unavailable due to market unbundling, or inaccurate due to aging infrastructure, non-documented tuning of controllers, or other factors. In this paper, we propose the use of a numerical approximation of the Fisher Information Matrix (nFIM) for efficient inference of dynamic model parameters. Thanks to the proposed numerical implementation, the method is scalable to Electromagnetic Transient (EMT) models, which can quickly become computationally complex even for small study systems. Case studies show that the nFIM is coherent with parameter variances of single- and multi-parameter least-squares estimators when applied to an IEEE 9-bus dynamic model with artificial measurements.
△ Less
Submitted 26 May, 2025;
originally announced May 2025.
-
Probabilistic Flexibility Aggregation of DERs for Ancillary Services Provision
Authors:
Matthieu Jacobs,
Mario Paolone
Abstract:
This paper presents a grid-aware probabilistic approach to compute the aggregated flexibility at the grid connection point (GCP) of active distribution networks (ADNs) to allow the participation of DERs in ancillary services (AS) markets. Specifically an optimal power flow (OPF) method using a linear network model is used to compute the aggregated capability for the provision of multiple AS. We st…
▽ More
This paper presents a grid-aware probabilistic approach to compute the aggregated flexibility at the grid connection point (GCP) of active distribution networks (ADNs) to allow the participation of DERs in ancillary services (AS) markets. Specifically an optimal power flow (OPF) method using a linear network model is used to compute the aggregated capability for the provision of multiple AS. We start from the method proposed in [1] and extend it to allow for optimizing the provision of multiple services simultaneously, ensure cost-effectiveness of the used DERs and handle uncertainties in a probabilistic way. The allocation of individual DERs power flexibilities accounts for the operational costs associated to the provision of different services and ensures cost-effectiveness while maximizing the value of the advertised aggregated flexibility, assuming known service prices. Empirical uncertainty sets are obtained to achieve a predefined coverage of the probability distribution in line with recent developments in the Nordic AS markets. Finally, a feeder-decomposition approach is proposed to ensure the methods applicability to realistic distribution networks with a large number of buses. Different case studies show the effectiveness of the method, highlight the importance of accounting for network constraints and illustrate its applicability to realistic distribution systems.
△ Less
Submitted 19 March, 2025;
originally announced March 2025.
-
Experimental Validation of Distributed Dispatching of Multiple Active Distribution Networks Using the ADMM
Authors:
Matthieu Jacobs,
Hanmin Cai,
Mario Paolone
Abstract:
This paper presents the experimental validation of a framework for the coordinated dispatch and control of multiple active distribution networks (ADNs) hosting distributed energy resource (DER). We show that the presented method, which builds further on work done in [1], effectively allows to control multiple ADNs in a distributed way to ensure they achieve a common objective without revealing inf…
▽ More
This paper presents the experimental validation of a framework for the coordinated dispatch and control of multiple active distribution networks (ADNs) hosting distributed energy resource (DER). We show that the presented method, which builds further on work done in [1], effectively allows to control multiple ADNs in a distributed way to ensure they achieve a common objective without revealing information on their DERs capabilities or grid model. This experimental validation is carried out using demonstrators at the DESL of EPFL and the NEST site at Empa, both in Switzerland. The coordination of the systems to share the flexibility of their controllable assets is demonstrated through a set of 24h experiments. Finally, the limitations of the method are discussed and future extensions proposed.
△ Less
Submitted 19 March, 2025;
originally announced March 2025.
-
Grid-Aware Islanding and Resynchronisation of AC/DC Microgrids
Authors:
Willem Lambrichts,
Jules Mace,
Drazen Dujic,
Mario Paolone
Abstract:
This paper proposes an optimal, grid-aware control framework for the islanding, island-operation and resynchronisation of hybrid AC/DC microgrids. The optimal control framework is based on a formally derived linearized load-flow model for multiterminal hybrid AC/DC networks. The load flow model integrates the AC grid, DC grid, and interfacing converters (IC) into a unified representation. This wor…
▽ More
This paper proposes an optimal, grid-aware control framework for the islanding, island-operation and resynchronisation of hybrid AC/DC microgrids. The optimal control framework is based on a formally derived linearized load-flow model for multiterminal hybrid AC/DC networks. The load flow model integrates the AC grid, DC grid, and interfacing converters (IC) into a unified representation. This work extends an existing load flow model to include the ICs' grid-forming operation.
In traditional islanding control frameworks, the grid-forming converter is typically interfaced with an energy storage system that can provide bidirectional power to maintain the power balance. The proposed framework, however, allows the ICs to operate as the grid-forming unit while being connected to a DC grid rather than a single resource. This configuration allows for a wider operating range and, thus, a more flexible control. Furthermore, the optimal grid-aware control framework can steer the system to ensure a feasible operation without any grid constraint violations before, during, and after the islanding manoeuvre. The framework also guarantees smooth transitions, i.e., without any significant transient behaviour, when transitioning between grid-connected and islanding operations. The optimal control framework is experimentally validated on a 27-bus hybrid AC/DC network consisting of 3 ICs that interface the AC and DC networks. The hybrid grid hosts various controllable and stochastic resources.
△ Less
Submitted 6 March, 2025;
originally announced March 2025.
-
A Synchrophasor Estimator Characterized by Attenuated Self-Interference and Robustness Against DC Offsets: the DCSOGI Interpolated DFT
Authors:
César García-Veloso,
Mario Paolone,
José María Maza-Ortega
Abstract:
The second-order generalized integrator (SOGI), which can be used to attenuate the self-interference of the fundamental tone, is unable to reject DC offsets on the input signal. Consequently, the performance of any SOGI based synchrophasor estimation (SE) technique might be compromised in the presence of such DC components. The current work presents a SE algorithm which adopts and enhanced SOGI fo…
▽ More
The second-order generalized integrator (SOGI), which can be used to attenuate the self-interference of the fundamental tone, is unable to reject DC offsets on the input signal. Consequently, the performance of any SOGI based synchrophasor estimation (SE) technique might be compromised in the presence of such DC components. The current work presents a SE algorithm which adopts and enhanced SOGI formulation, robust against DC, combined with a three-point IpDFT and a Hanning window. Two alternative formulations relying respectively on the use of two and three nominal fundamental period observation windows are proposed and assessed for simultaneous compliance with both phasor measurement unit (PMU) P and M performance classes. This is done by means of a simulated environment where all the operating conditions defined by the IEC/IEEE Std. 60255-118-1-2018 are evaluated simultaneously combined with a $10\%$ static DC and under two different noise levels. Furthermore, both formulations adopt a dedicated mechanism for the detection and correction of low amplitude $2^{nd}$ harmonic tones to ensure their compliance with the standard can be maintained in the presence of such disturbances even under off-nominal frequency conditions. Finally the resilience of both methods against multiple simultaneous harmonic interferences is also analyzed.
△ Less
Submitted 23 January, 2025;
originally announced January 2025.
-
Optimizing Experiments for Accurate Battery Circuit Parameters Estimation: Reduction and Adjustment of Frequency Set Used in Electrochemical Impedance Spectroscopy
Authors:
Vladimir Sovljanski,
Mario Paolone,
Sylvain Tant,
Damien Pierre Sainflou
Abstract:
In this paper, we study a suitable experimental design of electrochemical impedance spectroscopy (EIS) to reduce the number of frequency points while not significantly affecting the uncertainties of the estimated cell's equivalent circuit model (ECM) parameters. It is based on an E-optimal experimental design that aims to maximize the information about the ECM parameters collected by EIS measureme…
▽ More
In this paper, we study a suitable experimental design of electrochemical impedance spectroscopy (EIS) to reduce the number of frequency points while not significantly affecting the uncertainties of the estimated cell's equivalent circuit model (ECM) parameters. It is based on an E-optimal experimental design that aims to maximize the information about the ECM parameters collected by EIS measurements and, at the same time, minimize the overall uncertainty. In a numerical experiment, we first analyze to which extent reducing the number of measurement points at low frequencies affects the uncertainty of the estimated parameters. Secondly, we show that applying the frequency adjustments can lead to the same or even improved global uncertainty of ECM parameter estimates as with a higher number of measurements. This is numerically verified through a case study using the ECM parameters of a commercial battery cell.
△ Less
Submitted 10 January, 2025;
originally announced January 2025.
-
Achieving Dispatchability in Data Centers: Carbon and Cost-Aware Sizing of Energy Storage and Local Photovoltaic Generation
Authors:
Enea Figini,
Mario Paolone
Abstract:
Data centers are large electricity consumers due to the high consumption needs of servers and their cooling systems. Given the current crypto-currency and artificial intelligence trends, the data center electricity demand is bound to grow significantly. With the electricity sector being responsible for a large share of global greenhouse gas (GHG) emissions, it is important to lower the carbon foot…
▽ More
Data centers are large electricity consumers due to the high consumption needs of servers and their cooling systems. Given the current crypto-currency and artificial intelligence trends, the data center electricity demand is bound to grow significantly. With the electricity sector being responsible for a large share of global greenhouse gas (GHG) emissions, it is important to lower the carbon footprint of data centers to meet GHG emissions targets set by international agreements. Moreover, uncontrolled integration of data centers in power distribution grids contributes to increasing the stochasticity of the power system demand, thus increasing the need for capacity reserves, which leads to economic and environmental inefficiencies in the power grid operation. This work provides a method to size a PhotoVoltaic (PV) system and an Energy Storage System (ESS) for an existing data center looking to reduce both its carbon footprint and demand stochasticity via dispatching. The proposed scenario-based optimization framework allows to size the ESS and the PV system to minimize the expected operational and capital costs, along with the carbon footprint of the data center complex. The life cycle assessment of the resources, as well as the dynamic carbon emissions of the upstream power distribution grid, are accounted for while computing the day-ahead planning of the data center aggregated demand and PV generation. Case studies in different Swiss cantons and regions of Germany emphasize the need for location-aware sizing processes since the obtained optimal solutions strongly depend on the local electricity carbon footprint, cost and on the local irradiance conditions. Some regions show potential in carbon footprint reduction, while other regions do not.
△ Less
Submitted 2 January, 2025; v1 submitted 18 December, 2024;
originally announced December 2024.
-
Harmonic Stability Analysis of Microgrids with Converter-Interfaced Distributed Energy Resources, Part II: Case Studies
Authors:
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Mario Paolone
Abstract:
In Part I of this paper a method for the Harmonic Stability Assessment (HSA) of power systems with a high share of Converter-Interfaced Distributed Energy Resources (CIDERs) was proposed. Specifically, the Harmonic State-Space (HSS) model of a generic power system is derived through combination of the components HSS models. The HSS models of CIDERs and grid are based on Linear Time-Periodic (LTP)…
▽ More
In Part I of this paper a method for the Harmonic Stability Assessment (HSA) of power systems with a high share of Converter-Interfaced Distributed Energy Resources (CIDERs) was proposed. Specifically, the Harmonic State-Space (HSS) model of a generic power system is derived through combination of the components HSS models. The HSS models of CIDERs and grid are based on Linear Time-Periodic (LTP) models, capable of representing the coupling between different harmonics. In Part II, the HSA of a grid-forming, and two grid-following CIDERs (i.e., ex- and including the DC-side modelling) is performed. More precisely, the classification of the eigenvalues, the impact of the maximum harmonic order on the locations of the eigenvalues, and the sensitivity curves of the eigenvalues w.r.t. to control parameters are provided. These analyses allow to study the physical meaning and origin of the CIDERs eigenvalues. Additionally, the HSA is performed for a representative example system derived from the CIGRE low-voltage benchmark system. A case of harmonic instability is identified through the system eigenvalues, and validated with Time-Domain Simulations (TDS) in Simulink. It is demonstrated that, as opposed to stability analyses based on Linear Time-Invariant (LTI) models, the HSA is suitable for the detection of harmonic instability.
△ Less
Submitted 12 August, 2024;
originally announced August 2024.
-
Harmonic Stability Analysis of Microgrids with Converter-Interfaced Distributed Energy Resources, Part I: Modelling and Theoretical Foundations
Authors:
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Mario Paolone
Abstract:
This paper proposes a method for the Harmonic Stability Assessment (HSA) of power systems with a high share of Converter-Interfaced Distributed Energy Resources (CIDERs). To this end, the Harmonic State-Space (HSS) model of a generic power system is formulated by combining the HSS models of the resources and the grid in closed-loop configuration. The HSS model of the resources is obtained from the…
▽ More
This paper proposes a method for the Harmonic Stability Assessment (HSA) of power systems with a high share of Converter-Interfaced Distributed Energy Resources (CIDERs). To this end, the Harmonic State-Space (HSS) model of a generic power system is formulated by combining the HSS models of the resources and the grid in closed-loop configuration. The HSS model of the resources is obtained from the Linear Time Periodic (LTP) models of the CIDER components transformed to frequency domain using Fourier theory and Toeplitz matrices. Notably, the HSS of a CIDER is capable of representing the coupling between harmonic frequencies in detail. The HSS model of the grid is derived from the dynamic equations of the individual branch and shunt elements. The system matrix of the HSS models on power-system or resource level is employed for eigenvalue analysis in the context of HSA. A sensitivity analysis of the eigenvalue loci w.r.t. changes in model parameters, and a classification of eigenvalues into control-design variant, control-design invariant, and design invariant eigenvalues is proposed. A case of harmonic instability is identified by the HSA and validated via Time-Domain Simulations (TDS) in Simulink.
△ Less
Submitted 12 August, 2024;
originally announced August 2024.
-
Functional Basis Analysis for the Characterization of Power System Signal Dynamics: Formulation, Implementation and Validation
Authors:
Alexandra Karpilow,
Asja Derviskadic,
Mario Paolone
Abstract:
With the integration of distributed energy resources and the trend towards low-inertia power grids, the frequency and severity of grid dynamics is expected to increase. Conventional phasor-based signal processing methods are proving to be insufficient in the analysis of non-stationary AC voltage and current waveforms, while the computational complexity of many dynamic signal analysis techniques hi…
▽ More
With the integration of distributed energy resources and the trend towards low-inertia power grids, the frequency and severity of grid dynamics is expected to increase. Conventional phasor-based signal processing methods are proving to be insufficient in the analysis of non-stationary AC voltage and current waveforms, while the computational complexity of many dynamic signal analysis techniques hinders their deployment in operational embedded systems. This paper presents the Functional Basis Analysis (FBA), a signal processing tool capable of capturing the full broadband nature of signal dynamics in power grids while maintaining a streamlined design for real-time monitoring applications. Relying on the Hilbert transform and optimization techniques, the FBA can be user-engineered to identify and characterize combinations of several of the most common signal dynamics in power grids, including amplitude/phase modulations, frequency ramps and steps. This paper describes the theoretical basis and design of the FBA as well as the deployment of the algorithm in embedded hardware systems, with adaptations made to consider latency requirements, finite memory capacity, and fixed-point precision arithmetic. For validation, a PMU calibrator is used to evaluate and compare the algorithm's performance to state-of-the-art static and dynamic phasor methods. The test outcomes demonstrate the FBA method's suitability for implementation in embedded systems to improve grid situational awareness during severe grid events.
△ Less
Submitted 28 June, 2024;
originally announced June 2024.
-
Experimental Investigation of Repurposed Kaplan Turbines as Variable-Speed Propellers for Maximizing Frequency Containment Reserve
Authors:
Francesco Gerini,
Elena Vagnoni,
Martin Seydoux,
Rachid Cherkaoui,
Mario Paolone
Abstract:
This study explores the practical viability of repurposing aging Kaplan turbines into variable-speed propellers by employing full-size frequency converters. The motivation behind this approach is to improve the provision of \emph{Frequency Containment Reserve} (FCR) while reducing fatigue in the Kaplan blades servomechanism. We evaluate the performance of these modified Kaplan turbines against the…
▽ More
This study explores the practical viability of repurposing aging Kaplan turbines into variable-speed propellers by employing full-size frequency converters. The motivation behind this approach is to improve the provision of \emph{Frequency Containment Reserve} (FCR) while reducing fatigue in the Kaplan blades servomechanism. We evaluate the performance of these modified Kaplan turbines against the one of another hydro asset composed of the same Kaplan turbine hybridized with a \emph{Battery Energy Storage System} (BESS). Experiments are conducted on a one-of-its-kind reduced-scale model testing platform. Our findings reveal that Kaplan turbines repurposed as variable-speed propellers exhibit similar dynamic response characteristics compared to the standalone Kaplan operation, with the added benefit of effectively eliminating blade movements. Furthermore, the ability to control the speed increases the hydraulic efficiency for certain operating points. In summary, investment in variable speed technology emerges as a viable alternative to BESS-based hydropower hybridization.
△ Less
Submitted 6 May, 2024;
originally announced May 2024.
-
Grid-aware Scheduling and Control of Electric Vehicle Charging Stations for Dispatching Active Distribution Networks. Part-II: Intra-day and Experimental Validation
Authors:
Rahul K. Gupta,
Sherif Fahmy,
Max Chevron,
Enea Figini,
Mario Paolone
Abstract:
In Part-I, we presented an optimal day-ahead scheduling scheme for dispatching active distribution networks accounting for the flexibility provided by electric vehicle charging stations (EVCSs) and other controllable resources such as battery energy storage systems (BESSs). Part-II presents the intra-day control layer for tracking the dispatch plan computed from the day-ahead scheduling stage. The…
▽ More
In Part-I, we presented an optimal day-ahead scheduling scheme for dispatching active distribution networks accounting for the flexibility provided by electric vehicle charging stations (EVCSs) and other controllable resources such as battery energy storage systems (BESSs). Part-II presents the intra-day control layer for tracking the dispatch plan computed from the day-ahead scheduling stage. The control problem is formulated as model predictive control (MPC) with an objective to track the dispatch plan setpoint every 5 minutes, while actuated every 30 seconds. MPC accounts for the uncertainty of the power injections from stochastic resources (such as demand and generation from photovoltaic - PV plants) by short-term forecasts. MPC also accounts for the grid's operational constraints (i.e., the limits on the nodal voltages and the line power-flows) by a linearized optimal power flow (LOPF) model based on the power-flow sensitivity coefficients, and for the operational constraints of the controllable resources (i.e., BESSs and EVCSs). The proposed framework is experimentally validated on a real-life ADN at the EPFL's Distributed Electrical Systems Laboratory and is composed of a medium voltage (MV) bus connected to three low voltage distribution networks. It hosts two controllable EVCSs (172 kWp and 32 F~kWp), multiple PV plants (aggregated generation of 42~kWp), uncontrollable demand from office buildings (20 kWp), and two controllable BESSs (150kW/300kWh and 25kW/25kWh).
△ Less
Submitted 19 April, 2024;
originally announced April 2024.
-
Grid-aware Scheduling and Control of Electric Vehicle Charging Stations for Dispatching Active Distribution Networks. Part-I: Day-ahead and Numerical Validation
Authors:
Rahul K. Gupta,
Sherif Fahmy,
Max Chevron,
Riccardo Vasapollo,
Enea Figini,
Mario Paolone
Abstract:
This paper proposes a grid-aware scheduling and control framework for Electric Vehicle Charging Stations (EVCSs) for dispatching the operation of an active power distribution network. The framework consists of two stages. In the first stage, we determine an optimal day-ahead power schedule at the grid connection point (GCP), referred to as the dispatch plan. Then, in the second stage, a real-time…
▽ More
This paper proposes a grid-aware scheduling and control framework for Electric Vehicle Charging Stations (EVCSs) for dispatching the operation of an active power distribution network. The framework consists of two stages. In the first stage, we determine an optimal day-ahead power schedule at the grid connection point (GCP), referred to as the dispatch plan. Then, in the second stage, a real-time model predictive control is proposed to track the day-ahead dispatch plan using flexibility from EVCSs. The dispatch plan accounts for the uncertainties of vehicles connected to the EVCS along with other uncontrollable power injections, by day-ahead predicted scenarios. We propose using a Gaussian-Mixture-Model (GMM) for the forecasting of EVCS demand using the historical dataset on arrival, departure times, EV battery capacity, State-of-Charge (SoC) targets, etc. The framework ensures that the grid is operated within its voltage and branches power-flow operational bounds, modeled by a linearized optimal power-flow model, maintaining the tractability of the problem formulation. The scheme is numerically and experimentally validated on a real-life distribution network at the EPFL connected to two EVCSs, two batteries, three photovoltaic plants, and multiple heterogeneous loads. The day-ahead and real-time stages are described in Part-I and Part-II papers respectively.
△ Less
Submitted 19 April, 2024;
originally announced April 2024.
-
Ensuring Solution Uniqueness in Fixed-Point-Based Harmonic Power Flow Analysis with Converter-Interfaced Resources: Ex-post Conditions
Authors:
Antonio Di Pasquale,
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Mario Paolone
Abstract:
Recently, the authors of this paper proposed a method for the Harmonic Power-Flow (HPF) calculus in polyphase grids with widespread deployment of Converter-Interfaced Distributed Energy Resources (CIDERs). The HPF problem was formulated by integrating the hybrid nodal equations of the grid with a detailed representation of the CIDERs hardware, sensing, and controls as Linear Time-Periodic (LTP) sy…
▽ More
Recently, the authors of this paper proposed a method for the Harmonic Power-Flow (HPF) calculus in polyphase grids with widespread deployment of Converter-Interfaced Distributed Energy Resources (CIDERs). The HPF problem was formulated by integrating the hybrid nodal equations of the grid with a detailed representation of the CIDERs hardware, sensing, and controls as Linear Time-Periodic (LTP) systems, and solving the resulting mismatch equations using the Newton-Raphson (NR) method. This work introduces a novel problem formulation based on the fixed-point algorithm that, combined with the contraction property of the HPF problem, provides insights into the uniqueness of its solution. Notably, the effectiveness of the fixed-point formulation and the uniqueness of the solution are evaluated through numerical analyses conducted on a modified version of the CIGRE low-voltage benchmark microgrid.
△ Less
Submitted 19 March, 2024;
originally announced March 2024.
-
On the Use of Cramer-Rao Lower Bound for Least-Variance Circuit Parameters Identification of Li-ion Cells
Authors:
Vladimir Sovljanski,
Mario Paolone
Abstract:
Electrochemical Impedance Spectroscopy (EIS) and Equivalent Circuit Models (ECMs) are widely used to characterize the impedance and estimate parameters of electrochemical systems such as batteries. We use a generic ECM with ten parameters grouped to model different frequency regions of the Li-ion cell's impedance spectrum. We derive a noise covariance matrix from the measurement model and use it t…
▽ More
Electrochemical Impedance Spectroscopy (EIS) and Equivalent Circuit Models (ECMs) are widely used to characterize the impedance and estimate parameters of electrochemical systems such as batteries. We use a generic ECM with ten parameters grouped to model different frequency regions of the Li-ion cell's impedance spectrum. We derive a noise covariance matrix from the measurement model and use it to assign weights for the fitting technique. The paper presents two formulations of the parameters identification problem. Using the properties of the ECM EIS spectra, we propose a method to initialize ECM parameters for the Complex Non-linear Least Squares (CNLS) technique. The paper proposes a novel algorithm for designing the EIS experiments by applying the theory on Cramer-Rao Lower Bound (CRLB) and Fisher Information Matrix (FIM) to the identification problem. We show that contributions to the FIM elements strongly depend on the frequencies at which EIS is performed. Hence, the algorithm aims to adjust frequencies such that the most information about parameters is collected. This is done by minimizing the highest variance of ECM parameters defined by CRLB. Results of a numerical experiment show that the estimator is efficient, and frequency adjustment leads to more accurate ECM parameters' identification.
△ Less
Submitted 15 March, 2024;
originally announced March 2024.
-
Experimental Validation of a Grid-Aware Optimal Control of Hybrid AC/DC Microgrids
Authors:
Willem Lambrichts,
Jules Mace,
Mario Paolone
Abstract:
This paper presents the experimental validation of a grid-aware real-time control method for hybrid AC/DC microgrids. The optimal control is leveraged by the voltage sensitivity coefficients (SC) that are computed analytically using the close-form expression proposed in the authors' previous work. The SCs are based on the unified power flow model for hybrid AC/DC grids that accounts for the AC gri…
▽ More
This paper presents the experimental validation of a grid-aware real-time control method for hybrid AC/DC microgrids. The optimal control is leveraged by the voltage sensitivity coefficients (SC) that are computed analytically using the close-form expression proposed in the authors' previous work. The SCs are based on the unified power flow model for hybrid AC/DC grids that accounts for the AC grid, DC grid, and the Interfacing Converters (IC), which can operate in different control modes, e.g. voltage or power control. The SCs are used to express the grid constraints in the optimal control problem in a fully linear way and, therefore, allow for second- to subsecond control actions. The validation of the model is performed on the hybrid AC/DC grid, available at the EPFL. The network consists of 18 AC nodes, 8 DC nodes, and 4 converters to interface the AC and DC network. The network hosts multiple controllable and uncontrollable resources. The SC-based optimal control is validated in a generic experiment. It is shown that the real-time control is able to control the ICs optimally to redirect power through the DC grid, to avoid grid constraint violations while providing reactive power support to the upper layer AC grid. Furthermore, the computational time of the optimal control is analysed to validate its application in critical real-time applications.
△ Less
Submitted 1 November, 2023;
originally announced November 2023.
-
Probabilistic Load Forecasting of Distribution Power Systems based on Empirical Copulas
Authors:
Pål Forr Austnes,
Celia García-Pareja,
Fabio Nobile,
Mario Paolone
Abstract:
Accurate and reliable electricity load forecasts are becoming increasingly important as the share of intermittent resources in the system increases. Distribution System Operators (DSOs) are called to accurately forecast their production and consumption to place optimal bids in the day-ahead market. Forecasts must account for the volatility of weather-parameters that impacts both the production and…
▽ More
Accurate and reliable electricity load forecasts are becoming increasingly important as the share of intermittent resources in the system increases. Distribution System Operators (DSOs) are called to accurately forecast their production and consumption to place optimal bids in the day-ahead market. Forecasts must account for the volatility of weather-parameters that impacts both the production and consumption of electricity. If DSO-loads are small or lower-granularity forecasts are needed, parametric statistical methods may fail to provide reliable performance since they rely on a priori statistical distributions of the variables to forecast. In this paper, we introduce a Probabilistic Load Forecast (PLF) method based on Empirical Copulas (ECs). The model is datadriven, does not need a priori assumption on parametric distribution for variables, nor the dependence structure (copula). It employs a kernel density estimate of the underlying distribution using beta kernels that have bounded support on the unit hypercube. The method naturally supports variables with widely different distributions, such as weather data (including forecasted ones) and historic electricity consumption, and produces a conditional probability distribution for every time step in the forecast, which allows inferring the quantiles of interest. The proposed non-parametric approach differs significantly from previous forecasting methods based on copulas, which typically uses copulas to model hierarchical dependence. The bandwidth of the beta kernel density estimators is optimized using Integrated Square Error (ISE). We present results from an open dataset and showcase the strength of the model with respect to Quantile Regression (QR) using standard probabilistic evaluation metrics.
△ Less
Submitted 8 October, 2024; v1 submitted 5 October, 2023;
originally announced October 2023.
-
Analytically Computation of Sensitivity Coefficients in Hybrid AC/DC Micro-Grid
Authors:
Willem Lambrichts,
Mario Paolone
Abstract:
In this paper, we present a closed-form model for the analytical computation of the power flow sensitivity coefficients (SCs) for hybrid AC/DC networks. The SCs are defined as the partial derivates of the nodal voltages with respect to the active and reactive power injections. The proposed method is inspired by an existing SC computation process proposed for AC networks and here extended to includ…
▽ More
In this paper, we present a closed-form model for the analytical computation of the power flow sensitivity coefficients (SCs) for hybrid AC/DC networks. The SCs are defined as the partial derivates of the nodal voltages with respect to the active and reactive power injections. The proposed method is inspired by an existing SC computation process proposed for AC networks and here extended to include both the DC grid and the relevant AC/DC Interfacing Converters (ICs). The ICs can operate under different control modes i.e. voltage or power. Additionally, the model is able to compute the SCs for three-phase networks subjected to unbalanced loading conditions. The proposed method is numerically validated by means of a comparison with a detailed time-domain simulation model solved within the EMTP-RV simulation environment. Furthermore, we provide a formal proof regarding the uniqueness of the proposed SCs computational model for hybrid AC/DC networks.
△ Less
Submitted 1 November, 2023; v1 submitted 28 September, 2023;
originally announced September 2023.
-
General and Unified Model of the Power Flow Problem in Multiterminal AC/DC Networks
Authors:
Willem Lambrichts,
Mario Paolone
Abstract:
This paper proposes a generic and unified model of the power flow (PF) problem for multiterminal hybrid AC/DC networks. The proposed model is an extension of the standard AC-PF. The DC network is treated as an AC one and, in addition to the Slack, PV and PQ nodes, four new node types are introduced to model the DC buses and the buses connecting the AC/DC interfacing converters (IC). The unified mo…
▽ More
This paper proposes a generic and unified model of the power flow (PF) problem for multiterminal hybrid AC/DC networks. The proposed model is an extension of the standard AC-PF. The DC network is treated as an AC one and, in addition to the Slack, PV and PQ nodes, four new node types are introduced to model the DC buses and the buses connecting the AC/DC interfacing converters (IC). The unified model is solved using the Newton-Raphson method. The extended PF equations can be used in the presence of multiple ICs operating under different control modes. Compared to other recent works, the proposed method allows multiple ICs to regulate the DC voltage simultaneously. This corresponds to more realistic operational conditions that ensure redundancy and allow for more flexible control of the hybrid grid. The proposed model can be used for networks under unbalanced conditions and allows for an intentionally negative sequence power injection. In addition to the operational advantages of this method, it is shown that the computational performance of the proposed method is one order of magnitude better than that of other methods presented in the existing recent literature while having the same accuracy.
△ Less
Submitted 28 September, 2023;
originally announced September 2023.
-
Enhanced Frequency Containment Reserve Provision from Battery Hybridized Hydropower Plants: Theory and Experimental Validation
Authors:
Francesco Gerini,
Elena Vagnoni,
Martin Seydoux,
Rachid Cherkaoui,
Mario Paolone
Abstract:
This paper presents a solution to address wear and tear of Run-of-River (RoR) Hydropower Plants (HPPs) providing enhanced Frequency Containment Reserve (FCR). In this respect, the study proposes the integration of a Battery Energy Storage System (BESS) with RoR HPPs controlled by a double-layer Model Predictive Control (MPC). The upper layer MPC acts as a state of energy manager for the BESS, empl…
▽ More
This paper presents a solution to address wear and tear of Run-of-River (RoR) Hydropower Plants (HPPs) providing enhanced Frequency Containment Reserve (FCR). In this respect, the study proposes the integration of a Battery Energy Storage System (BESS) with RoR HPPs controlled by a double-layer Model Predictive Control (MPC). The upper layer MPC acts as a state of energy manager for the BESS, employing a forecast of the required regulating energy for the next hour. The lower-layer MPC optimally allocates the power set-point between the turbine and the BESS. Reduced-scale experiments are performed on a one-of-a-kind testing platform to validate the proposed MPC- based control considering a comparison with different control strategies and different BESS sizes. The results demonstrate superior performance of the proposed framework, compared to simpler techniques like dead-band control or to the standalone RoR scenario, leading to improved FCR provision, reduced servomechanism stress, and extended hydropower asset lifespan.
△ Less
Submitted 29 September, 2023; v1 submitted 27 September, 2023;
originally announced September 2023.
-
Computation of Ultra-Short-Term Prediction Intervals of the Power Prosumption in Active Distribution Networks
Authors:
Plouton Grammatikos,
Fabrizio Sossan,
Jean-Yves Le Boudec,
Mario Paolone
Abstract:
Microgrids and, in general, active distribution networks require ultra-short-term prediction, i.e., for sub-second time scales, for specific control decisions. Conventional forecasting methodologies are not effective at such time scales. To address this issue, we propose a non-parametric method for computing ultra short-term prediction intervals (PIs) of the power prosumption of generic electrical…
▽ More
Microgrids and, in general, active distribution networks require ultra-short-term prediction, i.e., for sub-second time scales, for specific control decisions. Conventional forecasting methodologies are not effective at such time scales. To address this issue, we propose a non-parametric method for computing ultra short-term prediction intervals (PIs) of the power prosumption of generic electrical-distribution networks. The method groups historical observations into clusters according to the values of influential variables. It is applied either to the original or to the differentiated power-prosumption time series. The clusters are considered statistically representative pools of future realizations of power prosumption (or its derivative). They are used to determine empirical PDFs and, by extracting the quantiles, to deliver PIs for respective arbitrary confidence levels. The models are validated a posteriori by carrying out a performance analysis that uses experimentally observed power-prosumption for different building types, thus allowing the identification of the dominant model.
△ Less
Submitted 19 September, 2023;
originally announced September 2023.
-
Experimental Validation of Model-less Robust Voltage Control using Measurement-based Estimated Voltage Sensitivity Coefficients
Authors:
Rahul Gupta,
Mario Paolone
Abstract:
Increasing adoption of smart meters and phasor measurement units (PMUs) in power distribution networks are enabling the adoption of data-driven/model-less control schemes to mitigate grid issues such as over/under voltages and power-flow congestions. However, such a scheme can lead to infeasible/inaccurate control decisions due to measurement inaccuracies. In this context, the authors' previous wo…
▽ More
Increasing adoption of smart meters and phasor measurement units (PMUs) in power distribution networks are enabling the adoption of data-driven/model-less control schemes to mitigate grid issues such as over/under voltages and power-flow congestions. However, such a scheme can lead to infeasible/inaccurate control decisions due to measurement inaccuracies. In this context, the authors' previous work proposed a robust measurement-based control scheme accounting for the uncertainties of the estimated models. In this scheme, a recursive least squares (RLS)-based method estimates the grid model (in the form of voltage magnitude sensitivity coefficients). Then, a robust control problem optimizes power set-points of distributed energy resources (DERs) such that the nodal voltage limits are satisfied. The estimated voltage sensitivity coefficients are used to model the nodal voltages, and the control robustness is achieved by accounting for their uncertainties. This work presents the first experimental validation of such a robust model-less control scheme on a real power distribution grid. The scheme is applied for voltage control by regulating two photovoltaic (PV) inverters connected in a real microgrid which is a replica of the CIGRE benchmark microgrid network at the EPFL Distributed Electrical Systems Laboratory.
△ Less
Submitted 26 April, 2023;
originally announced April 2023.
-
Computationally-Efficient Synchrophasor Estimation: Delayed in-quadrature Interpolated DFT
Authors:
César García Veloso,
Mario Paolone,
José María Maza Ortega
Abstract:
The paper proposes a synchropahsor estimation (SE) algorithm that leverages the use of a delayed in-quadrature complex signal to mitigate the self-interference of the fundamental tone. The estimator, which uses a three-point IpDFT combined with a three-cycle Hanning window, incorporates a new detection mechanism to iteratively estimate and remove the effects caused by interfering tones within the…
▽ More
The paper proposes a synchropahsor estimation (SE) algorithm that leverages the use of a delayed in-quadrature complex signal to mitigate the self-interference of the fundamental tone. The estimator, which uses a three-point IpDFT combined with a three-cycle Hanning window, incorporates a new detection mechanism to iteratively estimate and remove the effects caused by interfering tones within the out-of-band interference (OOBI) range. The main feature of the method is its ability to detect interfering tones with an amplitude lower than that adopted by the IEC/IEEE Std. 60255-118, this detection being notably challenging. Furthermore, it simultaneously satisfies all the accuracy requirements for the P and M phasor measurement unit (PMU) performance classes, while offering a reduction in the total computational cost compared to other state-of-the-art techniques. Despite an increase in total memory requirements, a preliminary analysis reveals its suitability for implementation on embedded devices.
△ Less
Submitted 15 April, 2023;
originally announced April 2023.
-
Harmonic Power-Flow Study of Hybrid AC/DC Grids with Converter-Interfaced Distributed Energy Resources
Authors:
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Yihui Zuo,
Mario Paolone
Abstract:
As the share of Converter-Interfaced Distributed Energy Resources (CIDERs) in power distribution systems increases, hybrid AC/DC distribution systems are drawing more interest. Indeed, CIDERs usually rely on DC power and hybrid AC/DC grids with few Network-Interfacing Converters (NICs) are a promising solution to decrease installation costs and conversion losses compared to a pure AC grid. However…
▽ More
As the share of Converter-Interfaced Distributed Energy Resources (CIDERs) in power distribution systems increases, hybrid AC/DC distribution systems are drawing more interest. Indeed, CIDERs usually rely on DC power and hybrid AC/DC grids with few Network-Interfacing Converters (NICs) are a promising solution to decrease installation costs and conversion losses compared to a pure AC grid. However, interactions between the AC and DC subsystem of a hybrid AC/DC grid can lead to undesirable amplification and propagation of harmonics. The authors of this paper have recently proposed a Harmonic Power-Flow (HPF) method that accurately represents the AC power flows including the coupling between different harmonics. The HPF framework is formulated through the mismatch equations of the nodal equations between the grid and the resource models and solved by a Newton Raphson algorithm. This paper updates the HPF method to model hybrid AC/DC grids interconnected through NICs. To this end, the model of the NICs and the resulting coupling between the AC and DC subsystems is included in the mismatch equations and the Jacobian matrix of the algorithm. The updated HPF method is applied to a typical hybrid AC/DC grid, and its accuracy is validated through detailed time-domain simulations with Simulink.
△ Less
Submitted 6 February, 2023;
originally announced February 2023.
-
Modelling of AC/DC Interactions of Converter-Interfaced Resources for Harmonic Power-Flow Studies in Microgrids
Authors:
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Yihui Zuo,
Federico Cecati,
Sante Pugliese,
Marco Liserre,
Mario Paolone
Abstract:
Power distribution systems experience a large-scale integration of Converter-Interfaced Distributed Energy Resources (CIDERs). As acknowledged by recent literature, the interaction of individual CIDER components and different CIDERs through the grid can lead to undesirable amplification of harmonic frequencies and, ultimately, compromise the distribution system stability. In this context, the inte…
▽ More
Power distribution systems experience a large-scale integration of Converter-Interfaced Distributed Energy Resources (CIDERs). As acknowledged by recent literature, the interaction of individual CIDER components and different CIDERs through the grid can lead to undesirable amplification of harmonic frequencies and, ultimately, compromise the distribution system stability. In this context, the interaction of the DC and AC sides of CIDERs has been shown to have a significant impact. In order to analyze and support the mitigation of such phenomena, the authors of this paper recently proposed a Harmonic Power-Flow (HPF) framework for polyphase grids with a high share of CIDERs. The framework considers the coupling between harmonics, but ignores the DC-side response of the CIDERs. Modelling the DC side and AC/DC converter introduces a nonlinearity into the CIDER model that needs to be approximated for the numerical solution of the HPF. This paper extends the CIDER model and HPF framework to address this aspect, whose inclusion is non-trivial. The extended HPF method is applied to a modified version of the CIGRE low-voltage benchmark microgrid. The results are compared to (i) time-domain simulations with Simulink, (ii) the predecessor of the extended HPF which neglects the DC side, and (iii) a classical decoupled HPF.
△ Less
Submitted 21 October, 2022; v1 submitted 15 June, 2022;
originally announced June 2022.
-
Model-less Robust Voltage Control in Active Distribution Networks using Sensitivity Coefficients Estimated from Measurements
Authors:
Rahul Gupta,
Fabrizio Sossan,
Mario Paolone
Abstract:
Measurement-rich power distribution networks may enable distribution system operators (DSOs) to adopt model-less and measurement-based monitoring and control of distributed energy resources (DERs) for mitigating grid issues such as over/under voltages and lines congestions. However, measurement-based monitoring and control applications may lead to inaccurate control decisions due to measurement er…
▽ More
Measurement-rich power distribution networks may enable distribution system operators (DSOs) to adopt model-less and measurement-based monitoring and control of distributed energy resources (DERs) for mitigating grid issues such as over/under voltages and lines congestions. However, measurement-based monitoring and control applications may lead to inaccurate control decisions due to measurement errors. In particular, estimation models relying on regression-based schemes result in significant errors in the estimates (e.g., nodal voltages) especially for measurement devices with high Instrument Transformer (IT) classes. The consequences are detrimental to control performance since this may lead to infeasible decisions. This work proposes a model-less robust voltage control accounting for the uncertainties of measurement-based estimated voltage sensitivity coefficients. The coefficients and their uncertainties are obtained using a recursive least squares (RLS)-based online estimation, updated whenever new measurements are available. This formulation is applied to control distributed controllable photovoltaic (PV) generation in a distribution network to restrict the voltage within prescribed limits. The proposed scheme is validated by simulating a CIGRE low-voltage system interfacing multiple controllable PV plants.
△ Less
Submitted 11 January, 2022;
originally announced January 2022.
-
Coordinated Day-ahead Dispatch of Multiple Power Distribution Grids hosting Stochastic Resources: An ADMM-based Framework
Authors:
Rahul Gupta,
Sherif Fahmy,
Mario Paolone
Abstract:
This work presents an optimization framework to aggregate the power and energy flexibilities in an interconnected power distribution systems. The aggregation framework is used to compute the day-ahead dispatch plans of multiple and interconnected distribution grids operating at different voltage levels. Specifically, the proposed framework optimizes the dispatch plan of an upstream medium voltage…
▽ More
This work presents an optimization framework to aggregate the power and energy flexibilities in an interconnected power distribution systems. The aggregation framework is used to compute the day-ahead dispatch plans of multiple and interconnected distribution grids operating at different voltage levels. Specifically, the proposed framework optimizes the dispatch plan of an upstream medium voltage (MV) grid accounting for the flexibility offered by downstream low voltage (LV) grids and the knowledge of the uncertainties of the stochastic resources. The framework considers grid, i.e., operational limits on the nodal voltages, lines, and transformer capacity using a linearized grid model, and controllable resources' constraints. The dispatching problem is formulated as a stochastic-optimization scheme considering uncertainty on stochastic power generation and demands and the voltage imposed by the upstream grid. The problem is solved by a distributed optimization method relying on the Alternating Direction Method of Multipliers (ADMM) that splits the main problem into an aggregator problem (solved at the MV-grid level) and several local problems (solved at the MV-connected-controllable-resources and LV-grid levels). The use of distributed optimization enables a decentralized dispatch computation where the centralized aggregator is agnostic about the parameters/models of the participating resources and downstream grids. The framework is validated for interconnected CIGRE medium- and low-voltage networks hosting heterogeneous stochastic and controllable resources.
△ Less
Submitted 13 April, 2022; v1 submitted 10 January, 2022;
originally announced January 2022.
-
Optimal Grid-Forming Control of Battery Energy Storage Systems Providing Multiple Services: Modelling and Experimental Validation
Authors:
Francesco Gerini,
Yihui Zuo,
Rahul Gupta,
Elena Vagnoni,
Rachid Cherkaoui,
Mario Paolone
Abstract:
This paper proposes and experimentally validates a joint control and scheduling framework for a grid-forming converter-interfaced BESS providing multiple services to the electrical grid. The framework is designed to dispatch the operation of a distribution feeder hosting heterogeneous prosumers according to a dispatch plan and provide frequency containment reserve and voltage control as additional…
▽ More
This paper proposes and experimentally validates a joint control and scheduling framework for a grid-forming converter-interfaced BESS providing multiple services to the electrical grid. The framework is designed to dispatch the operation of a distribution feeder hosting heterogeneous prosumers according to a dispatch plan and provide frequency containment reserve and voltage control as additional services. The framework consists of three phases. In the day-ahead scheduling phase, a robust optimization problem is solved to compute the optimal dispatch plan and frequency droop coefficient, accounting for the uncertainty of the aggregated prosumption. In the intra-day phase, a model predictive control algorithm is used to compute the power set-point for the BESS to achieve the tracking of the dispatch plan. Finally, in a real-time stage, the power setpoint originated by the dispatch tracking is converted into a feasible frequency set-point for the grid forming converter by means of a convex optimisation problem accounting for the capability curve of the power converter. The proposed framework is experimentally validated by using a grid-scale 720 kVA/560 kWh BESS connected to a 20 kV distribution feeder of the EPFL hosting stochastic prosumption and PV generation.
△ Less
Submitted 19 October, 2021;
originally announced October 2021.
-
Local Effects of Grid-Forming Converters Providing Frequency Regulation to Bulk Power Grids
Authors:
Antonio Zecchino,
Francesco Gerini,
Yihui Zuo,
Rachid Cherkaoui,
Mario Paolone,
Elena Vagnoni
Abstract:
The progressive displacing of conventional generation in favour of renewable energy sources requires restoring an adequate capacity of regulating power to ensure reliable operation of power systems. Battery Energy Storage Systems (BESSs) are considered to be promising assets to restore suitable frequency regulation capacity levels. BESSs are typically connected to the grid with power-converters, a…
▽ More
The progressive displacing of conventional generation in favour of renewable energy sources requires restoring an adequate capacity of regulating power to ensure reliable operation of power systems. Battery Energy Storage Systems (BESSs) are considered to be promising assets to restore suitable frequency regulation capacity levels. BESSs are typically connected to the grid with power-converters, able to operate in either grid-forming or grid-following modes. This paper quantitatively assesses the impact on the local distribution grid of BESSs providing frequency regulation to bulk power systems. Specific metrics are proposed to compare the performance of grid-forming and grid-following control. Experimental results are obtained taking advantage of a 720 kVA/500 kWh BESS connected to the 20 kV distribution grid of the EPFL campus. The quantitative evaluation based on suitably proposed metrics confirms the superior performance of the grid-forming strategy, compared to the grid-following one.
△ Less
Submitted 11 October, 2021;
originally announced October 2021.
-
Harmonic Power-Flow Study of Polyphase Grids with Converter-Interfaced Distributed Energy Resources, Part II: Model Library and Validation
Authors:
Johanna Kristin Maria Becker,
Andreas Martin Kettner,
Lorenzo Reyes-Chamorro,
Zhixiang Zou,
Marco Liserre,
Mario Paolone
Abstract:
In Part I, a method for the Harmonic Power-Flow (HPF) study of three-phase power grids with Converter-Interfaced Distributed Energy Resources (CIDERs) is proposed. The method is based on generic and modular representations of the grid and the CIDERs, and explicitly accounts for coupling between harmonics. In Part II, the HPF method is validated. First, the applicability of the modeling framework i…
▽ More
In Part I, a method for the Harmonic Power-Flow (HPF) study of three-phase power grids with Converter-Interfaced Distributed Energy Resources (CIDERs) is proposed. The method is based on generic and modular representations of the grid and the CIDERs, and explicitly accounts for coupling between harmonics. In Part II, the HPF method is validated. First, the applicability of the modeling framework is demonstrated on typical grid-forming and grid-following CIDERs. Then, the HPF method is implemented in Matlab and compared against time-domain simulations with Simulink. The accuracy of the models and the performance of the solution algorithm are assessed for individual resources and a modified version of the CIGRÉ low-voltage benchmark microgrid (i.e., with additional unbalanced components). The observed maximum errors are 6.3E-5 p.u. w.r.t. voltage magnitude, 1.3E-3 p.u. w.r.t. current magnitude, and 0.9 deg w.r.t. phase. Moreover, the scalability of the method is assessed w.r.t. the number of CIDERs and the maximum harmonic order ($\leqslant$25). For the maximum problem size, the execution time of the HPF method is 6.52 sec, which is 5 times faster than the time-domain simulation. The convergence of the method is robust w.r.t. the choice of the initial point, and multiplicity of solutions has not been observed.
△ Less
Submitted 1 November, 2021; v1 submitted 23 June, 2021;
originally announced June 2021.
-
Harmonic Power-Flow Study of Polyphase Grids with Converter-Interfaced Distributed Energy Resources, Part I: Modelling Framework and Algorithm
Authors:
Andreas Martin Kettner,
Lorenzo Reyes-Chamorro,
Johanna Kristin Maria Becker,
Zhixiang Zou,
Marco Liserre,
Mario Paolone
Abstract:
Power distribution systems are experiencing a large-scale integration of Converter-Interfaced Distributed Energy Resources (CIDERs). This complicates the analysis and mitigation of harmonics, whose creation and propagation are facilitated by the interactions of converters and their controllers through the grid. In this paper, a method for the calculation of the so-called Harmonic Power-Flow (HPF)…
▽ More
Power distribution systems are experiencing a large-scale integration of Converter-Interfaced Distributed Energy Resources (CIDERs). This complicates the analysis and mitigation of harmonics, whose creation and propagation are facilitated by the interactions of converters and their controllers through the grid. In this paper, a method for the calculation of the so-called Harmonic Power-Flow (HPF) in three-phase grids with CIDERs is proposed. The distinguishing feature of this HPF method is the generic and modular representation of the system components. Notably, as opposed to most of the existing approaches, the coupling between harmonics is explicitly considered. The HPF problem is formulated by combining the hybrid nodal equations of the grid with the closed-loop transfer functions of the CIDERs, and solved using the Newton-Raphson method. The grid components are characterized by compound electrical parameters, which allow to represent both transposed or non-transposed lines. The CIDERs are represented by modular linear time-periodic systems, which allows to treat both grid-forming and grid-following control laws. The method's accuracy and computational efficiency are confirmed via time-domain simulations of the CIGRÉ low-voltage benchmark microgrid. This paper is divided in two parts, which focus on the development (Part I) and the validation (Part II) of the proposed method.
△ Less
Submitted 1 November, 2021; v1 submitted 23 June, 2021;
originally announced June 2021.
-
Performance assessment of Synchronous Condensers vs Voltage Source Converters providing grid-forming functions
Authors:
Dorsan Lepour,
Mario Paolone,
Guillaume Denis,
Carmen Cardozo,
Thibault Prevost,
Emeline Guiu
Abstract:
Having sufficient grid-forming sources is one of the necessary conditions to guarantee the stability in a power system hosting a very large share of inverter-based generation. The grid-forming function has been historically fulfilled by synchronous machines. However, with the appropriate control, it can also be provided by voltage source converters (VSC). This work presents a comparison between tw…
▽ More
Having sufficient grid-forming sources is one of the necessary conditions to guarantee the stability in a power system hosting a very large share of inverter-based generation. The grid-forming function has been historically fulfilled by synchronous machines. However, with the appropriate control, it can also be provided by voltage source converters (VSC). This work presents a comparison between two technologies with grid-forming capability: the VSC with a grid-forming control coupled with an adequate energy storage system, and the synchronous condensers (SC). Both devices are compared regarding their inertial response, as well as their contribution to the system strength and short-circuit current for an equivalent capacity expressed in terms of apparent power and inertial reserve. Their behaviour following grid disturbances is assessed through time-domain simulations based on detailed electromagnetic transient (EMT) models. The results show that both devices achieve similar performance in the time-scale of seconds. For shorter time-windows, however, they present a different behavior: the SC ensures a better stiffness in the first tens of ms following the disturbance, while the VSC offers a faster resynchronization.
△ Less
Submitted 7 June, 2021;
originally announced June 2021.
-
Frequency stability assessment of modern power systems: models definition and parameters identification
Authors:
Francesco Conte,
Stefano Massucco,
Mario Paolone,
Giacomo-Piero Schiapparelli,
Federico Silvestro,
Yihui Zuo
Abstract:
One of the fundamental concerns in the operation of modern power systems is the assessment of their frequency stability in case of inertia-reduction induced by the large share of power electronic interfaced resources. Within this context, the paper proposes a framework that, by making use of linear models of the frequency response of different types of power plants, including also grid--forming an…
▽ More
One of the fundamental concerns in the operation of modern power systems is the assessment of their frequency stability in case of inertia-reduction induced by the large share of power electronic interfaced resources. Within this context, the paper proposes a framework that, by making use of linear models of the frequency response of different types of power plants, including also grid--forming and grid-following converters, is capable to infer a numerically tractable dynamical model to be used in frequency stability assessment. Furthermore, the proposed framework makes use of models defined in a way such that their parameters can be inferred from real-time measurements feeding a classical least squares estimator. The paper validates the proposed framework using a full-replica of the dynamical model of the IEEE 39 bus system simulated in a real-time platform.
△ Less
Submitted 15 April, 2021;
originally announced April 2021.
-
Leverage Point Identification Method for LAV-Based State Estimation
Authors:
Mathias Dorier,
Guglielmo Frigo,
Ali Abur,
Mario Paolone
Abstract:
The state estimation problem can be solved through different methods. In terms of robustness, an effective approach is represented by the Least Absolute Value (LAV) estimator, though vulnerable to leverage points. Based on a previously proposed theorem, in this paper we enunciate, and rigorously demonstrate, a new lemma that proves the identifiability of leverage points in LAV-based state estimati…
▽ More
The state estimation problem can be solved through different methods. In terms of robustness, an effective approach is represented by the Least Absolute Value (LAV) estimator, though vulnerable to leverage points. Based on a previously proposed theorem, in this paper we enunciate, and rigorously demonstrate, a new lemma that proves the identifiability of leverage points in LAV-based state estimation. On the basis of these theoretical foundations, we propose an algorithm for leverage point identification whose performance is validated by means of extensive numerical simulations and compared against more traditional approaches, like Projection Statistics (PS). The obtained results confirm that the proposed method outperforms PS and represents a significant enhancement for LAV-based state estimators as it correctly identifies all the leverage points, independently of the accuracy or the presence of measurement gross errors. A dedicated application example with respect to power system state estimation is finally included and discussed.
△ Less
Submitted 10 August, 2020;
originally announced August 2020.
-
Grid-aware Distributed Model Predictive Control of Heterogeneous Resources in a Distribution Network: Theory and Experimental Validation
Authors:
Rahul Kumar Gupta,
Fabrizio Sossan,
Mario Paolone
Abstract:
In this paper, we propose and experimentally validate a scheduling and control framework for distributed energy resources (DERs) that achieves to track a day-ahead dispatch plan of a distribution network hosting controllable and stochastic heterogeneous resources while respecting the local grid constraints on nodal voltages and lines ampacities. The framework consists of two algorithmic layers. In…
▽ More
In this paper, we propose and experimentally validate a scheduling and control framework for distributed energy resources (DERs) that achieves to track a day-ahead dispatch plan of a distribution network hosting controllable and stochastic heterogeneous resources while respecting the local grid constraints on nodal voltages and lines ampacities. The framework consists of two algorithmic layers. In the first one (day-ahead scheduling), we determine an aggregated dispatch plan. In the second layer (real-time control), a distributed model predictive control (MPC) determines the active and reactive power set-points of the DERs so that their aggregated contribution tracks the dispatch plan while obeying to DERs operational constraints as well as the grids ones. The proposed framework is experimentally validated on a real-scale microgrid that reproduces the network specifications of the CIGRE microgrid benchmark system.
△ Less
Submitted 6 August, 2020;
originally announced August 2020.
-
Real-time Control of Battery Energy Storage Systems to Provide Ancillary Services Considering Voltage-Dependent Capability of DC-AC Converters
Authors:
Zhao Yuan,
Antonio Zecchino,
Rachid Cherkaoui,
Mario Paolone
Abstract:
Frequency response and voltage support are vital ancillary services for power grids. In this paper, we design and experimentally validate a real-time control framework for battery energy storage systems (BESSs) to provide ancillary services to power grids. The objective of the control system is to utilize the full capability of the BESSs to provide ancillary services. We take the voltage-dependent…
▽ More
Frequency response and voltage support are vital ancillary services for power grids. In this paper, we design and experimentally validate a real-time control framework for battery energy storage systems (BESSs) to provide ancillary services to power grids. The objective of the control system is to utilize the full capability of the BESSs to provide ancillary services. We take the voltage-dependent capability curve of the DC-AC converter and the security requirements of BESSs as constraints of the control system. The initial power set-points are obtained based on the droop control approach. To guarantee the feasibility of the power set-points with respect to both the converter capability and BESS security constraints, the final power set-points calculation is formulated as a nonconvex optimization problem. A convex and computationally efficient reformulation of the original control problem is then proposed. We prove that the proposed convex optimization gives the global optimal solution to the original nonconvex problem. We improve the computational performance of this algorithm by discretizing the feasible region of the optimization model. We achieve a 100 ms update time of the controller setpoint computation in the experimental validation of the utility-scale 720 kVA / 560 kWh BESS on the EPFL campus.
△ Less
Submitted 3 May, 2021; v1 submitted 23 June, 2020;
originally announced June 2020.
-
Siting and Sizing of Energy Storage Systems: Towards a Unified Approach for Transmission and Distribution System Operators for Reserve Provision and Grid Support
Authors:
Stefano Massucco,
Paola Pongiglione,
Federico Silvestro,
Mario Paolone,
Fabrizio Sossan
Abstract:
This paper presents a method to determine the optimal location, energy capacity, and power rating of distributed battery energy storage systems at multiple voltage levels to accomplish grid control and reserve provision. We model operational scenarios at a one-hour resolution, where deviations of stochastic loads and renewable generation (modeled through scenarios) from a day-ahead unit commitment…
▽ More
This paper presents a method to determine the optimal location, energy capacity, and power rating of distributed battery energy storage systems at multiple voltage levels to accomplish grid control and reserve provision. We model operational scenarios at a one-hour resolution, where deviations of stochastic loads and renewable generation (modeled through scenarios) from a day-ahead unit commitment and violations of grid constraints are compensated by either dispatchable power plants (conventional reserves) or injections from battery energy storage systems. By plugging-in costs of conventional reserves and capital costs of converter power ratings and energy storage capacity, the model is able to derive requirements for storage deployment that achieve the technical-economical optimum of the problem. The method leverages an efficient linearized formulation of the grid constraints of both the HV (High Voltage) and MV (Medium Voltage) grids while still retaining fundamental modeling aspects of the power system (such as transmission losses, effect of reactive power, OLTC at the MV/HV interface, unideal efficiency of battery energy storage systems) and models of conventional generator. A proof-of-concept by simulations is provided with the IEEE 9-bus system coupled with the CIGRE' benchmark system for MV grids, realistic costs of power reserves, active power rating and energy capacity of batteries, and load and renewable generation profile from real measurements.
△ Less
Submitted 20 April, 2020;
originally announced April 2020.
-
Effect of Voltage Source Converters with Electrochemical Storage Systems on Dynamics of Reduced-inertia Bulk Power Grids
Authors:
Yihui Zuo,
Mario Paolone,
Fabrizio. Sossan
Abstract:
A major concern associated to the massive connection of distributed energy resources is the increasing share of power electronic interfaces resulting in the global inertia reduction of power systems. The recent literature advocated the use of voltage source converter (VSC) interfaced battery energy storage system (BESS) as a potential way to counterbalance this lack of inertia. However, the impact…
▽ More
A major concern associated to the massive connection of distributed energy resources is the increasing share of power electronic interfaces resulting in the global inertia reduction of power systems. The recent literature advocated the use of voltage source converter (VSC) interfaced battery energy storage system (BESS) as a potential way to counterbalance this lack of inertia. However, the impact of VSCs on the dynamics of reduced-inertia grids is not well understood especially with respect to large transmission grids interfacing a mix of rotating machines and resources interfaced with power electronics. In this regards, we propose an extension of the IEEE 39-bus test network used to quantify the impact of VSCs on reduced-inertia grids. In this respect, a reduced-inertia 39-bus system is obtained by replacing 4 synchronous generators in the original 10-synchronous machine system, with 4 wind power plants modeled as aggregated type-3 wind turbines. Then, a large-scale BESS is integrated into the reduced-inertia network via a three-level neutral-point clamped (NPC) converter, thereby to be used for studying the impact of VSC on the dynamics of the inertia-reduced power system, as well as for comparing different VSC controls. The proposed models are implemented on a real-time simulator to conduct post-contingency analysis, respectively, for the original power system and the reduced-inertia one, with and without the BESS-VSC.
△ Less
Submitted 19 April, 2020; v1 submitted 13 October, 2019;
originally announced October 2019.
-
Optimal Provision of Concurrent Primary Frequency and Local Voltage Control from a BESS Considering Variable Capability Curves: Modelling and Experimental Assessment
Authors:
Antonio Zecchino,
Zhao Yuan,
Fabrizio Sossan,
Rachid Cherkaoui,
Mario Paolone
Abstract:
This paper proposes a control method for battery energy storage systems (BESSs) to provide concurrent primary frequency and local voltage regulation services. The actual variable active and reactive power capability of the converter, along with the state-of-charge of the BESS, are jointly considered by the optimal operating point calculation process within the real-time operation. The controller o…
▽ More
This paper proposes a control method for battery energy storage systems (BESSs) to provide concurrent primary frequency and local voltage regulation services. The actual variable active and reactive power capability of the converter, along with the state-of-charge of the BESS, are jointly considered by the optimal operating point calculation process within the real-time operation. The controller optimizes the provision of grid services, considering the measured grid and battery statuses and predicting the battery DC voltage as a function of the current trajectory using a three-time-constant model (TTC). A computationally-efficient algorithm is proposed to solve the formulated optimal control problem. Experimental tests validate the proposed concepts and show the effectiveness of the employed control framework on a commercial utility-scale 720 kVA/560 kWh BESS.
△ Less
Submitted 8 April, 2020; v1 submitted 9 October, 2019;
originally announced October 2019.
-
Optimal Allocation of ESSs in Active Distribution Networks to achieve their Dispatchability
Authors:
Ji Hyun Yi,
Rachid Cherkaoui,
Mario Paolone
Abstract:
This paper presents a method for the optimal siting and sizing of energy storage systems (ESSs) in active distribution networks (ADNs) to achieve their dispatchability. The problem formulation accounts for the uncertainty inherent to the stochastic nature of distributed energy sources and loads. Thanks to the operation of ESSs, the main optimization objective is to minimize the dispatch error, whi…
▽ More
This paper presents a method for the optimal siting and sizing of energy storage systems (ESSs) in active distribution networks (ADNs) to achieve their dispatchability. The problem formulation accounts for the uncertainty inherent to the stochastic nature of distributed energy sources and loads. Thanks to the operation of ESSs, the main optimization objective is to minimize the dispatch error, which accounts for the mismatch between the realization and prediction of the power profile at the ADN connecting point to the upper layer grid, while respecting the grid voltages and ampacity constraints. The proposed formulation relies on the so-called Augmented Relaxed Optimal Power Flow (AR-OPF) method: it expresses a convex full AC optimal power flow, which is proven to provide a global optimal and exact solution in the case of radial power grids. The AR-OPF is coupled with the proposed dispatching control resulting in a two-level optimization problem. In the first block, the site and size of the ESSs are decided along with the level of dispatchability that the ADN can achieve. Then, in the second block, the adequacy of the ESS allocations and the feasibility of the grid operating points are verified over operating scenarios using the Benders decomposition technique. Consequently, the optimal size and site of the ESSs are adjusted. To validate the proposed method, simulations are conducted on a real Swiss ADN hosting a large amount of stochastic Photovoltaic (PV) generation.
△ Less
Submitted 14 April, 2020; v1 submitted 27 September, 2019;
originally announced September 2019.
-
Performance Assessment of Kron Reduction in the Numerical Analysis of Polyphase Power Systems
Authors:
Andreas Martin Kettner,
Mario Paolone
Abstract:
This paper investigates the impact of Kron reduction on the performance of numerical methods applied to the analysis of unbalanced polyphase power systems. Specifically, this paper focuses on power-flow study, state estimation, and voltage stability assessment. For these applications, the standard Newton-Raphson method, linear weighted-least-squares regression, and homotopy continuation method are…
▽ More
This paper investigates the impact of Kron reduction on the performance of numerical methods applied to the analysis of unbalanced polyphase power systems. Specifically, this paper focuses on power-flow study, state estimation, and voltage stability assessment. For these applications, the standard Newton-Raphson method, linear weighted-least-squares regression, and homotopy continuation method are used, respectively. The performance of the said numerical methods is assessed in a series of simulations, in which the zero-injection nodes of a test system are successively eliminated through Kron reduction.
△ Less
Submitted 16 July, 2019;
originally announced July 2019.
-
Beyond Phasors: Continuous-Spectrum Modeling of Power Systems using the Hilbert Transform
Authors:
Asja Derviškadić,
Guglielmo Frigo,
Mario Paolone
Abstract:
Modern power systems are at risk of largely reducing the inertia of generation assets and prone to experience extreme dynamics. The consequence is that, during electromechanical transients triggered by large contingencies, transmission of electrical power may take place in a broad spectrum well beyond the single fundamental component. Traditional modeling approaches rely on the phasor representati…
▽ More
Modern power systems are at risk of largely reducing the inertia of generation assets and prone to experience extreme dynamics. The consequence is that, during electromechanical transients triggered by large contingencies, transmission of electrical power may take place in a broad spectrum well beyond the single fundamental component. Traditional modeling approaches rely on the phasor representation derived from the Fourier Transform (FT) of the signal under analysis. During large transients, though, FT-based analysis may fail to accurately identify the fundamental component parameters, in terms of amplitude, frequency and phase. In this paper, we propose an alternative approach relying on the Hilbert Transform (HT), that, in view of the possibility to identify the whole spectrum, enables the tracking of signal dynamics. We compare FT- and HT-based approaches during representative operating conditions, i.e., amplitude modulations, frequency ramps and step changes, in synthetic and real-world datasets. We further validate the approaches using a contingency analysis on the IEEE 39-bus.
△ Less
Submitted 26 June, 2019;
originally announced June 2019.
-
PMU-Based ROCOF Measurements: Uncertainty Limits and Metrological Significance in Power System Applications
Authors:
Guglielmo Frigo,
Asja Derviskadic,
Yihui Zuo,
Mario Paolone
Abstract:
In modern power systems, the Rate-of-Change-of-Frequency (ROCOF) may be largely employed in Wide Area Monitoring, Protection and Control (WAMPAC) applications. However, a standard approach towards ROCOF measurements is still missing. In this paper, we investigate the feasibility of Phasor Measurement Units (PMUs) deployment in ROCOF-based applications, with a specific focus on Under-Frequency Load…
▽ More
In modern power systems, the Rate-of-Change-of-Frequency (ROCOF) may be largely employed in Wide Area Monitoring, Protection and Control (WAMPAC) applications. However, a standard approach towards ROCOF measurements is still missing. In this paper, we investigate the feasibility of Phasor Measurement Units (PMUs) deployment in ROCOF-based applications, with a specific focus on Under-Frequency Load-Shedding (UFLS). For this analysis, we select three state-of-the-art window-based synchrophasor estimation algorithms and compare different signal models, ROCOF estimation techniques and window lengths in datasets inspired by real-world acquisitions. In this sense, we are able to carry out a sensitivity analysis of the behavior of a PMU-based UFLS control scheme. Based on the proposed results, PMUs prove to be accurate ROCOF meters, as long as the harmonic and inter-harmonic distortion within the measurement pass-bandwidth is scarce. In the presence of transient events, the synchrophasor model looses its appropriateness as the signal energy spreads over the entire spectrum and cannot be approximated as a sequence of narrow-band components. Finally, we validate the actual feasibility of PMU-based UFLS in a real-time simulated scenario where we compare two different ROCOF estimation techniques with a frequency-based control scheme and we show their impact on the successful grid restoration.
△ Less
Submitted 21 March, 2019;
originally announced March 2019.
-
A Generalized Index for Static Voltage Stability of Unbalanced Polyphase Power Systems including Thévenin Equivalents and Polynomial Models
Authors:
Andreas Martin Kettner,
Mario Paolone
Abstract:
This paper proposes a Voltage Stability Index (VSI) suitable for unbalanced polyphase power systems. To this end, the grid is represented by a polyphase multiport network model (i.e., compound hybrid parameters), and the aggregate behavior of the devices in each node by Thévenin Equivalents (TEs) and Polynomial Models (PMs), respectively. The proposed VSI is a generalization of the known L-index,…
▽ More
This paper proposes a Voltage Stability Index (VSI) suitable for unbalanced polyphase power systems. To this end, the grid is represented by a polyphase multiport network model (i.e., compound hybrid parameters), and the aggregate behavior of the devices in each node by Thévenin Equivalents (TEs) and Polynomial Models (PMs), respectively. The proposed VSI is a generalization of the known L-index, which is achieved through the use of compound electrical parameters, and the incorporation of TEs and PMs into its formal definition. Notably, the proposed VSI can handle unbalanced polyphase power systems, explicitly accounts for voltage-dependent behavior (represented by PMs), and is computationally inexpensive. These features are valuable for the operation of both transmission and distribution systems. Specifically, the ability to handle the unbalanced polyphase case is of particular value for distribution systems. In this context, it is proven that the compound hybrid parameters required for the calculation of the VSI do exist under practical conditions (i.e., for lossy grids). The proposed VSI is validated against state-of-the-art methods for voltage stability assessment using a benchmark system which is based on the IEEE 34-node feeder.
△ Less
Submitted 14 June, 2019; v1 submitted 26 September, 2018;
originally announced September 2018.
-
Dispatch and Primary Frequency Control with Electrochemical Storage: a System-wise Verification
Authors:
Yihui Zuo,
Fabrizio Sossan,
Mokhtar Bozorg,
Mario Paolone
Abstract:
Uncertainty levels in forecasting of renewable generation and demand are known to affect the amount of reserve required to operate the power grid with a given level of reliability. In this paper, we quantify the effects on the system reserve and reliability, due to the local dispatch of stochastic demand and renewable generation. The analysis is performed considering the model of the IEEE 39-bus s…
▽ More
Uncertainty levels in forecasting of renewable generation and demand are known to affect the amount of reserve required to operate the power grid with a given level of reliability. In this paper, we quantify the effects on the system reserve and reliability, due to the local dispatch of stochastic demand and renewable generation. The analysis is performed considering the model of the IEEE 39-bus system, with detailed dynamic models of conventional generation, wind generation, demand and an under-frequency load shedding mechanism. The analysis compares to cases: the base case, where renewable generation and demand power are stochastic and the power reserve is provided by conventional generation, against the case where the operation of traditionally stochastic resources is dispatched according to pre-established dispatch plans thanks to controlling local flexibility. Simulations reproduce the post-contingency dynamic behavior of the grid due to outages of generators. The contingencies are selected to trigger under frequency load shedding mechanisms, hence to demonstrate the different levels of system operation reliability for the two case studies. Simulation results show that dispatching traditionally stochastic generation scores better regarding to expected energy not served, producing an increase of the system reliability.
△ Less
Submitted 15 June, 2018;
originally announced June 2018.
-
Under Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF
Authors:
Asja Derviškadić,
Yihui Zuo,
Guglielmo Frigo,
Mario Paolone
Abstract:
The paper describes a distributed under-frequency load shedding and load restoration scheme, that exploits frequency and Rate-of-Change-of-Frequency (ROCOF) measurements produced by Phasor Measurement Units (PMUs) as detectors of a large contingency. The paper further discusses the appropriateness of using the synchrophasor model for estimating ROCOF during fast transients following a severe gener…
▽ More
The paper describes a distributed under-frequency load shedding and load restoration scheme, that exploits frequency and Rate-of-Change-of-Frequency (ROCOF) measurements produced by Phasor Measurement Units (PMUs) as detectors of a large contingency. The paper further discusses the appropriateness of using the synchrophasor model for estimating ROCOF during fast transients following a severe generation-load imbalance. The performance of the proposed relaying scheme is compared with a frequency-only based strategy, by means of a real-time digital simulator implementing the time-domain full-replica model of the IEEE 39 bus system.
△ Less
Submitted 2 May, 2018;
originally announced May 2018.
-
An ADMM-based Coordination and Control Strategy for PV and Storage to Dispatch Stochastic Prosumers: Theory and Experimental Validation
Authors:
Rahul Gupta,
Fabrizio Sossan,
Enrica Scolari,
Emil Namor,
Luca Fabietti,
Colin Jones,
Mario Paolone
Abstract:
This paper describes a two-layer control and coordination framework for distributed energy resources. The lower layer is a real-time model predictive control (MPC) executed at 10 s resolution to achieve fine tuning of a given energy set-point. The upper layer is a slower MPC coordination mechanism based on distributed optimization, and solved with the alternating direction method of multipliers (A…
▽ More
This paper describes a two-layer control and coordination framework for distributed energy resources. The lower layer is a real-time model predictive control (MPC) executed at 10 s resolution to achieve fine tuning of a given energy set-point. The upper layer is a slower MPC coordination mechanism based on distributed optimization, and solved with the alternating direction method of multipliers (ADMM) at 5 minutes resolution. It is needed to coordinate the power flow among the controllable resources such that enough power is available in real-time to achieve a pre-established energy trajectory in the long term. Although the formulation is generic, it is developed for the case of a battery system and a curtailable PV facility to dispatch stochastic prosumption according to a trajectory at 5 minutes resolution established the day before the operation. The proposed method is experimentally validated in a real-life setup to dispatch the operation of a building with rooftop PV generation (i.e., 101 kW average load, 350 kW peak demand, 82 kW peak PV generation) by controlling a 560 kWh/720 kVA battery and a 13 kW peak curtailable PV facility.
△ Less
Submitted 20 March, 2018;
originally announced March 2018.
-
Control of Battery Storage Systems for the Simultaneous Provision of Multiple Services
Authors:
Emil Namor,
Fabrizio Sossan,
Rachid Cherkaoui,
Mario Paolone
Abstract:
In this paper, we propose a control framework for a battery energy storage system to provide simultaneously multiple services to the electrical grid. The objective is to maximise the battery exploitation from these services in the presence of uncertainty (load, stochastic distributed generation, grid frequency). The framework is structured in two phases. In a period-ahead phase, we solve an optimi…
▽ More
In this paper, we propose a control framework for a battery energy storage system to provide simultaneously multiple services to the electrical grid. The objective is to maximise the battery exploitation from these services in the presence of uncertainty (load, stochastic distributed generation, grid frequency). The framework is structured in two phases. In a period-ahead phase, we solve an optimization problem that allocates the battery power and energy budgets to the different services. In the subsequent real-time phase the control set-points for the deployment of such services are calculated separately and superimposed. The control framework is first formulated in a general way and then casted in the problem of providing dispatchability of a medium voltage feeder in conjunction to primary frequency control. The performance of the proposed framework are validated by simulations and real-scale experi- ments, performed with a grid-connected 560 kWh/720 kVA Li-ion battery energy storage system.
△ Less
Submitted 12 October, 2018; v1 submitted 2 March, 2018;
originally announced March 2018.
-
On the Properties of the Compound Nodal Admittance Matrix of Polyphase Power Systems
Authors:
Andreas Martin Kettner,
Mario Paolone
Abstract:
Most techniques for power system analysis model the grid by exact electrical circuits. For instance, in power flow study, state estimation, and voltage stability assessment, the use of admittance parameters (i.e., the nodal admittance matrix) and hybrid parameters is common. Moreover, network reduction techniques (e.g., Kron reduction) are often applied to decrease the size of large grid models (i…
▽ More
Most techniques for power system analysis model the grid by exact electrical circuits. For instance, in power flow study, state estimation, and voltage stability assessment, the use of admittance parameters (i.e., the nodal admittance matrix) and hybrid parameters is common. Moreover, network reduction techniques (e.g., Kron reduction) are often applied to decrease the size of large grid models (i.e., with hundreds or thousands of state variables), thereby alleviating the computational burden. However, researchers normally disregard the fact that the applicability of these methods is not generally guaranteed. In reality, the nodal admittance must satisfy certain properties in order for hybrid parameters to exist and Kron reduction to be feasible. Recently, this problem was solved for the particular cases of monophase and balanced triphase grids. This paper investigates the general case of unbalanced polyphase grids. Firstly, conditions determining the rank of the so-called compound nodal admittance matrix and its diagonal subblocks are deduced from the characteristics of the electrical components and the network graph. Secondly, the implications of these findings concerning the feasibility of Kron reduction and the existence of hybrid parameters are discussed. In this regard, this paper provides a rigorous theoretical foundation for various applications in power system analysis
△ Less
Submitted 5 October, 2018; v1 submitted 23 December, 2017;
originally announced December 2017.
-
Unsupervised Disaggregation of PhotoVoltaic Production from Composite Power Flow Measurements of Heterogeneous Prosumers
Authors:
Fabrizio Sossan,
Lorenzo Nespoli,
Vasco Medici,
Mario Paolone
Abstract:
We consider the problem of estimating the unobserved amount of photovoltaic (PV) generation and demand in a power distribution network starting from measurements of the aggregated power flow at the point of common coupling (PCC) and local global horizontal irradiance (GHI). The estimation principle relies on modeling the PV generation as a function of the measured GHI, enabling the identification…
▽ More
We consider the problem of estimating the unobserved amount of photovoltaic (PV) generation and demand in a power distribution network starting from measurements of the aggregated power flow at the point of common coupling (PCC) and local global horizontal irradiance (GHI). The estimation principle relies on modeling the PV generation as a function of the measured GHI, enabling the identification of PV production patterns in the aggregated power flow measurements. Four estimation algorithms are proposed: the first assumes that variability in the aggregated PV generation is given by variations of PV generation, the next two use a model of the demand to improve estimation performance, and the fourth assumes that, in a certain frequency range, the aggregated power flow is dominated by PV generation dynamics. These algorithms leverage irradiance transposition models to explore several azimuth/tilt configurations and explain PV generation patterns from multiple plants with non-uniform installation characteristics. Their estimation performance is compared and validated with measurements from a real-life setup including 4 houses with rooftop PV installations and battery systems for PV self-consumption.
△ Less
Submitted 15 January, 2019; v1 submitted 15 June, 2017;
originally announced June 2017.